background image

4�10�3�5� Power status�

TAll the Modbus map addresses are hexadecimal.

The

0x04 function is implemented for this variable.

This variable indicates the quadrant in which the unit is operating.

Table 21:Modbus memory map: Power status

Power status

Variable

Address

Default value

Power status

7D1

-

The variable format is shown in

Table 22:

Table 22:Variable format: Power status�

Bit 7 Bit 6 Bit 5 Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

0

0

0

1: Capacitive

1: Inductive

1: Generated

1: Consumed

4�10�3�6�

Unit configuration variables.

All the Modbus map addresses are hexadecimal.

The

0x04 and 0x10 functions are implemented for this variable.

The unit’s Modbus function does not check whether the variables recorded are within the

correct margins, they are only checked when they are read from the EEPROM. So if any

parameter is recorded with an incorrect value the unit will be configured with its default value.

The Modbus configuration will not take effect until the unit is reset.

4�10�3�6�1�

Transformation ratios�

Table 23:Modbus memory map: Transformation ratios�

Transformation ratios

Configuration variable

(1) (2)

Address

Valid data margin

Default

value

Voltage primary

2710 - 2711

1 - 599999

1

Voltage secondary

2712

1 - 999

1

Current primary

2713

1 - 10000

5

Current secondary

2714

1: .../1A

5: ../5 A

5

(1)

All variables must be programmed at the same time.

(2)

Voltage ratio x Current ratio < 600000.

Note: The ratio is between the primary and the secondary.

67

Instruction Manual

CVM-C10