CIRCUTOR CVM-C10 Series User Manual
Page 67
![background image](https://www.manualsdir.com/files/767651/content/doc067.png)
4�10�3�5� Power status�
TAll the Modbus map addresses are hexadecimal.
The
0x04 function is implemented for this variable.
This variable indicates the quadrant in which the unit is operating.
Table 21:Modbus memory map: Power status
Power status
Variable
Address
Default value
Power status
7D1
-
The variable format is shown in
Table 22:Variable format: Power status�
Bit 7 Bit 6 Bit 5 Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
1: Capacitive
1: Inductive
1: Generated
1: Consumed
4�10�3�6�
Unit configuration variables.
All the Modbus map addresses are hexadecimal.
The
0x04 and 0x10 functions are implemented for this variable.
The unit’s Modbus function does not check whether the variables recorded are within the
correct margins, they are only checked when they are read from the EEPROM. So if any
parameter is recorded with an incorrect value the unit will be configured with its default value.
The Modbus configuration will not take effect until the unit is reset.
4�10�3�6�1�
Transformation ratios�
Table 23:Modbus memory map: Transformation ratios�
Transformation ratios
Configuration variable
(1) (2)
Address
Valid data margin
Default
value
Voltage primary
2710 - 2711
1 - 599999
1
Voltage secondary
2712
1 - 999
1
Current primary
2713
1 - 10000
5
Current secondary
2714
1: .../1A
5: ../5 A
5
(1)
All variables must be programmed at the same time.
(2)
Voltage ratio x Current ratio < 600000.
Note: The ratio is between the primary and the secondary.
67
Instruction Manual
CVM-C10