Unit terminals, Cvm-c10 instruction manual – CIRCUTOR CVM-C10 Series User Manual
Page 10
![background image](https://www.manualsdir.com/files/767651/content/doc010.png)
3.3.- UNIT TERMINALS
3�3�1�- List of terminals, CVM-C10-ITF, CVM-C10-MC and CVM-C10-mV models
Table 2:List of terminals of the CVM-C10-ITF, CVM-C10-MC and CVM-C10-mV�
Unit terminals
1 : A1 Auxiliary power supply.
13: I2, digital input 2 / tariff selection
2: A2 Auxiliary power supply.
14: V
L1,
Voltage input L1
3: Rc, Common relay output
15: V
L2,
Voltage input L2
4: R2, Relay output 2
16: V
L3
,Voltage input L3
5: R1, Relay output 1
17: N, Neutral
6: CT, Common digital output.
18: S1
,
Current input L1
7: T2, Digital output 2
19: S2, Current input L1
8: T1, Digital output 1
20: S1, Current input L2
9: A(+), RS485
21: S2, Current input L2
10: B(-), RS485
22: S1, Current input L3
11: GND, for RS485 and digital inputs
23: S
2
, Current input L3
12: I1, digital input 1 / tariff selection
1
2
3
4
5
6
7
8
9
10 11 12
13
14
15
16 17
18 19 20
21 22 23
POWER SUPPLY
INPUTS
A
(+) B(-)
GND
RS485
S1
S2
S1
S2 S1
S2
L1
P1
P2
L2
L3
300V ~
Ph-N
Ph-Ph
520V ~
N
V
L3
L2
V
L1
V
P1
P2 P1
P2
I1 I2
OUTPUTS
Rc R2 R1
Tc T2 T1
S0- S0+ S0+
Figure 1:Terminals of the CVM-C10-ITF, CVM-C10-MC and CVM-C10-mV�
10
CVM-C10
Instruction Manual