Chapter 7: HART Channel Configuration, Data, and Status

79

Table 7.6 (Generic CIP Configuration)

Unconnected Message Header

Field

Value

Definition

Message Type

“CIP Generic”

Control and Information Protocol (CIP) A native communications protocol used
on Allen-Bradley’s ControlNet communication network.

Service Code

0x32

Class Name

0xB0

Instance Name

0x01

Object Attribute

Leave blank

Source

?

The tag defining the data sent to the HART module

Number of elements

?

The number of elements defined by the command that is used

Destination

?

The tag where the reply data will be written

The MSG configuration screen is then loaded with the data from table 7.6.
See figure below.

Figure 7.8 (Message Configuration Dialog)

After the configuration screen is loaded with the data, the actual module
specific commands are loaded into the MSG source tag. When the MSG
instruction executes, the module specific command is passed to the module
via the MSG "source" tag and the reply data is passed to the MSG
"destination" tag. The module specific commands include, HART
suspension
, HART resume, get device information, and the HART pass-
through commands
. The tables on the following pages show the format
for each module specific command.

Note: The source length should be large enough to accommodate the
HART message string.