Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status

39

Table 5.1b

Tag Name

Data Type

Style

Description

If8h0Configuration.ChXInputRange

1

SINT

DEC

Configures the channel's input range.
Input ranges include:
0 = -10.25 to 10.25V
1 = 0 to 5.125V
2 = 0 to 10.25V
3 = 0 to 20.58 mA
4 = 3.42 mA to 20.58 mA

If8h0Configuration.ChXDigitalFilter

1

INT

DEC

A non-zero value enables the filter,
providing a time constant in
milliseconds used in a first order lag
filter to smooth the input signal. If non-
zero, must be greater than twice the
RTS rate.
0 to 20100 msec

If8h0Configuration.ChXRateAlarmLimit

1

REAL

FLOAT The trigger point for the rate alarm

status bit which will set if the input
signal changes at a rate faster than the
configured rate alarm. Configured in
user scaling units per second.

If8h0Configuration.ChXLowSignal

1

REAL

FLOAT One of four points used in scaling. The

low signal represents the minimum
input range.

If8h0Configuration.ChXHighSignal

1

REAL

FLOAT One of four points used in scaling. The

high signal represents the maximum
input range.

If8h0Configuration.ChXLowEngineering

1

REAL

FLOAT One of four points used in scaling. The

low engineering represents the
minimum scaled range.

If8h0Configuration.ChXHighEngineering

1

REAL

FLOAT One of four points used in scaling. The

high engineering represents the
maximum scaled range.

If8h0Configuration.ChXLowAlarm

1

REAL

FLOAT The low process alarm trigger point.

Enter the value in terms of engineering
units.

If8h0Configuration.ChXHighAlarm

1

REAL

FLOAT The high process alarm trigger point.

Enter the value in terms of engineering
units.

If8h0Configuration.ChXLowLowAlarm

1

REAL

FLOAT The low low process alarm trigger point.

Enter the value in terms of engineering
units.

1

X represents the module channel number (0 to 7).