Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status
55
Table 6.1d
Tag Name
Data Type Style Description
Of8h0Configuration.ChXIdleValue
1
FLOAT
REAL Defines the value, in engineering
units, the output should take when
the connection transitions to Program
mode. This function is only active
when bit 1 is set in the ChXConfigBits
tag.
Of8h0Configuration.ChXLowSignal
1
FLOAT
REAL One of four points used in scaling.
The low signal represents the
minimum output range.
Of8h0Configuration.ChXHighSignal
1
FLOAT
REAL One of four points used in scaling.
The high signal represents the
maximum output range.
Of8h0Configuration.ChXLowEngineering
1
FLOAT
REAL One of four points used in scaling.
The low engineering represents the
minimum scaled range.
Of8h0Configuration.ChXHighEngineering
1
FLOAT
REAL One of four points used in scaling.
The high engineering represents the
maximum scaled range.
Of8h0Configuration.ChXLowClamp
1
FLOAT
REAL Defines the minimum analog output
value the channel is allowed to
achieve.
Of8h0Configuration.ChXHighClamp
1
FLOAT
REAL Defines the maximum analog output
value the channel is allowed to
achieve.
Of8h0Configuration.ChXCalBias
1
FLOAT
REAL A user configurable offset added
directly to the measured analog value
for the channel.
Of8h0Configuration.ChXSlot0Code
1
SINT
DEC HART slot 0 transmitter variable
assignment code. Refer to chapter 7
for more information.
Of8h0Configuration.ChXSlot1Code
1
SINT
DEC HART slot 1 transmitter variable
assignment code. Refer to chapter 7
for more information.
Of8h0Configuration.ChXSlot2Code
1
SINT
DEC HART slot 2 transmitter variable
assignment code. Refer to chapter 7
for more information.
Of8h0Configuration.ChXSlot3Code
1
SINT
DEC HART slot 3 transmitter variable
assignment code. Refer to chapter 7
for more information.
1
X represents the module channel number (0 to 7).