Spectrum Controls 1756sc-OF8H Series A User Manual
Page 68
54 ControlLogix
™
Analog HART Modules
Table 6.1c
Tag Name
Data Type Style Description
Of8h0Configuration.ChXConfigBits.8
1
BOOL
DEC Hold for initialization
0 = Feature disabled
1 = The channel will hold, or not
change, until initialized with a value
within 0.1% of full scale of its current
value when one of the following
conditions occurs: Module initial
connection (power-up), module
transitions from program mode back
to run mode, module reestablishes
communication after a fault.
Of8h0Configuration.ChXConfigBits.9
1
BOOL
DEC Enables HART communication for the
channel.
0 = HART disabled
1 = HART Enabled
Of8h0Configuration.ChXConfigBits.10
1
BOOL
DEC Unused
Set to zero
Of8h0Configuration.ChXConfigBits.11
1
BOOL
DEC Unused
Set to zero
Of8h0Configuration.ChXConfigBits.12
1
BOOL
DEC Unused
Set to zero
Of8h0Configuration.ChXConfigBits.13
1
BOOL
DEC Unused
Set to zero
Of8h0Configuration.ChXConfigBits.14
1
BOOL
DEC Unused
Set to zero
Of8h0Configuration.ChXConfigBits.15
1
BOOL
DEC Unused
Set to zero
Of8h0Configuration.ChXOutputRange
1
INT
DEC Configures the channel’s output
range.
0 = +/-10 VDC
1 = 0 to 20mA
2 = 4 to 20mA
Of8h0Configuration.ChXMaxRampRate
1
FLOAT
REAL Configures the maximum rate at
which the output value may change.
Active only if bits 0, 1 or 2 are set in
the ChXConfigBits tag. Entered in
user scaling units per second.
Of8h0Configuration.ChXFaultValue
1
Defines the value, in engineering
units, the output should take if a
communications fault occurs when bit
0 is set in the ChXConfigBits tag.
1
X represents the module channel number (0 to 7).