54 ControlLogix

Analog HART Modules

Table 6.1c

Tag Name

Data Type Style Description

Of8h0Configuration.ChXConfigBits.8

1

BOOL

DEC Hold for initialization

0 = Feature disabled
1 = The channel will hold, or not
change, until initialized with a value
within 0.1% of full scale of its current
value when one of the following
conditions occurs: Module initial
connection (power-up), module
transitions from program mode back
to run mode, module reestablishes
communication after a fault.

Of8h0Configuration.ChXConfigBits.9

1

BOOL

DEC Enables HART communication for the

channel.
0 = HART disabled
1 = HART Enabled

Of8h0Configuration.ChXConfigBits.10

1

BOOL

DEC Unused

Set to zero

Of8h0Configuration.ChXConfigBits.11

1

BOOL

DEC Unused

Set to zero

Of8h0Configuration.ChXConfigBits.12

1

BOOL

DEC Unused

Set to zero

Of8h0Configuration.ChXConfigBits.13

1

BOOL

DEC Unused

Set to zero

Of8h0Configuration.ChXConfigBits.14

1

BOOL

DEC Unused

Set to zero

Of8h0Configuration.ChXConfigBits.15

1

BOOL

DEC Unused

Set to zero

Of8h0Configuration.ChXOutputRange

1

INT

DEC Configures the channel’s output

range.
0 = +/-10 VDC
1 = 0 to 20mA
2 = 4 to 20mA

Of8h0Configuration.ChXMaxRampRate

1

FLOAT

REAL Configures the maximum rate at

which the output value may change.
Active only if bits 0, 1 or 2 are set in
the ChXConfigBits tag. Entered in
user scaling units per second.

Of8h0Configuration.ChXFaultValue

1

Defines the value, in engineering
units, the output should take if a
communications fault occurs when bit
0 is set in the ChXConfigBits tag.

1

X represents the module channel number (0 to 7).