Spectrum Controls 1756sc-OF8H Series A User Manual
Page 66
![background image](/manuals/742122/66/background.png)
52 ControlLogix
™
Analog HART Modules
C o n f i g u r a t i o n
C o n f i g u r a t i o n
C o n f i g u r a t i o n
C o n f i g u r a t i o n
C o n f i g u r a t i o n
T
TT
T
Taaaaags f
gs f
gs f
gs f
gs for the
or the
or the
or the
or the
1 7 5 6 s c - O F 8 H
1 7 5 6 s c - O F 8 H
1 7 5 6 s c - O F 8 H
1 7 5 6 s c - O F 8 H
1 7 5 6 s c - O F 8 H
The following tags allow for custom configuration of the module. These
tags can be found within the controller scope under the tag name
Of8h0Configuration.
Table 6.1a
Tag Name
Data Type
Style Description
Of8h0Configuration
Of8hConfigurationBlock NA
Module configuration
Of8h0Configuration.ConfigRevision
SINT
DEC Controls multiple owner connections.
0 = Always connect, overwrite w/new
configuration.
1 = Only connect if configuration
matches existing configuration.
Of8h0Configuration.ProgToFaultEn
SINT
DEC The program to fault enable bit
determines how the outputs should
behave if a communications fault
were to occur while the output
module is in the program mode.
0 = Outputs will remain in their
configured program state despite a
communications fault occurring.
1 = will cause the outputs to
transition to their programmed fault
state if a communications fault
occurs while in the program state.
Of8h0Configuration.Spare
INT
DEC Unused
Set to zero
Of8h0Configuration.ChXConfigBits
1
INT
BIN
This is a set of individual channel
configuration bits which enable
various functions for the associated
channel.
Of8h0Configuration.ChXConfigBits.0
1
BOOL
DEC Enables ramping of the output value
to a user defined fault value
(ChXFaultValue)
0 = Feature disabled
1 = During a fault condition the
associated channel will ramp to the
value stored in the ChXFaultValue tag
at a rate defined by the value stored
in the ChXMaxRampRate.
Of8h0Configuration.ChXConfigBits.1
1
BOOL
DEC Enables ramping of the output value
to a user defined idle value
(ChXIdleValue)
0 = Feature disabled
1 = When the PLC is in program
mode the associated channel will
ramp to the value stored in the
ChXIdleValue tag at a rate defined by
the value stored in the
ChXMaxRampRate.
1
X represents the module channel number (0 to 7).