beautypg.com

Spectrum Controls 1756sc-OF8H Series A User Manual

Page 54

background image

40

ControlLogix

Analog HART Modules

Table 5.1c

Tag Name

Data Type Style

Description

If8h0Configuration.ChXHighHighAlarm

1

REAL

FLOAT The high high process alarm trigger

point. Enter the value in terms of
engineering units.

If8h0Configuration.ChXAlarmDeadband

1

REAL

FLOAT Forms a deadband around the process

alarms which causes the
corresponding process alarm status
bit to remain set until the input moves
beyond the trigger point by greater
than the amount of the alarm
deadband.

If8h0Configuration.ChXCalBias

1

REAL

FLOAT Offset to add to channel analog value

If8h0Configuration.HandleTimeout

INT

DEC

There is a handle timeout associated
with the final reply message. After the
module obtaines the requested
information from the HART device, it
will start the HandleTimeout timer
(duration defined by the
HandleTimeout tag). The replay
message will be kept in memory
during the HandleTimeout period.
After the timeout occurs or after the
message is retrieved by the pass-
through response query command, the
storage buffer will be discarded, and
another pass through message will be
serviced without being rejected.
HandleTimeout is in the range of 1 to
255 seconds.

If8h0Configuration.ModuleConfigBits

INT

BIN

Module function settings

If8h0Configuration.ModuleConfigBits.0

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.1

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.2

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.3

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.4

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.5

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.6

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.7

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.8

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.9

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.10

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.11

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.12

BOOL

DEC

Reserved set to zero

If8h0Configuration.ModuleConfigBits.13

BOOL

DEC

Reserved set to zero

1

X represents the module channel number (0 to 7).

This manual is related to the following products: