Spectrum Controls 1756sc-OF8H Series A User Manual
Page 67
Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status
53
Table 6.1b
Tag Name
Data Type Style Description
Of8h0Configuration.ChXConfigBits.2
1
BOOL
DEC Enables ramping of the output value
when the PLC is in RUN mode.
0 = Feature disabled
1 = When the PLC is in RUN mode
the associated channel will ramp to a
new output level at a rate defined by
the value stored in the
ChXMaxRampRate tag.
Of8h0Configuration.ChXConfigBits.3
1
BOOL
DEC Selects the behavior of the output
channel when transitioning into
Program mode.
0 = Hold last state
1 = go to the value stored in the
ChXIdleValue tag.
Of8h0Configuration.ChXConfigBits.4
1
BOOL
DEC Selects the behavior of the output
channel when a communication fault
occurs.
0 = Hold last state
1 = go to the value stored in the
ChXFaultValue tag.
Of8h0Configuration.ChXConfigBits.5
1
BOOL
DEC Enables latching for the clamp limit
alarms.
0 = Feature disabled
1 = Clamp limit alarm will remain set
until an unlatch service is explicitly
sent to the channel or alarm.
Of8h0Configuration.ChXConfigBits.6
1
BOOL
DEC Enables latching for all four process
alarms: low, low low, high, and high
high.
0 = Alarms unlatched
1 = process alarms will remain set
until an unlatch service is explicitly
sent to the channel or alarm.
Of8h0Configuration.ChXConfigBits.7
1
BOOL
DEC Disable alarms
0 = Alarms enabled
1 = Disable all alarms
1
X represents the module channel number (0 to 7).