ControlLogix

Analog HART Modules

Table 5.3c

Tag Name

Data Type

Style

Description

If8h0Input.ChanStatus

SINT[8]

BIN

An array of 8 SINT which display
general status for each channel.

If8h0Input.ChanStatus[X]

1

SINT

BIN

General channel status byte

If8h0Input.ChanStatus[X].0

1

BOOL

DEC

User value exceeded high high limit.
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].1

1

BOOL

DEC

User value exceeded low low limit.
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].2

1

BOOL

DEC

User value exceeded high limit.
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].3

1

BOOL

DEC

User value exceeded low limit.
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].4

1

BOOL

DEC

Specified ramp rate exceeded.
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].5

1

BOOL

DEC

Over Range alarm
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].6

1

BOOL

DEC

Under Range alarm
0 = No alarm
1 = Alarm

If8h0Input.ChanStatus[X].7

1

BOOL

DEC

Channel calibration fault
0 = No fault
1 = Fault

If8h0Input.ChanData

REAL[8]

FLOAT An array of 8 floating point registers

which display the analog data for
each channel in engineering units.

If8h0Input.ChanData[X]

1

REAL

FLOAT Channel analog data in engineering

units

1

X represents the module channel number (0 to 7).