ERROR CODES
___________________________________________________________________
Error No.
Message / Action
10-12
107
Data window 3, channel 4 reverse setpoint too high.
The Data window 3 reverse setpoint of the channel
indicated by the error code is set to a value
greater than 125% of the channel rating.
1)
Check the MACH RATING setting in the Config menu
for correctness.
2)
Adjust the indicated setpoint to a setting less
than 125% of the channel rating.
108
Data window 3, chan 1 high setpoint < low setpoint.
109
Data window 3, chan 2 high setpoint < low setpoint.
110
Data window 3, chan 3 high setpoint < low setpoint.
111
Data window 3, chan 4 high setpoint < low setpoint.
The Data window 3 high setpoint of the channel
indicated by the error code is set to a value less
than the low setpoint.
1)
Adjust the high or low setpoint so that the high
setpoint is greater than the low setpoint.
112
Data window 4, channel 1 high setpoint too high.
113
Data window 4, channel 2 high setpoint too high.
114
Data window 4, channel 3 high setpoint too high.
115
Data window 4, channel 4 high setpoint too high.
The Data window 4 high setpoint of the channel
indicated by the error code is set to a value
greater than 125% of the channel rating.
1)
Check the MACH RATING setting in the Config menu
for correctness.
2)
Adjust the indicated setpoint to a setting less
than 125% of the channel rating.
116
Data window 4, channel 1 low setpoint too high.