ERROR CODES
___________________________________________________________________
Error No.
Message / Action
10-7
048
Channel 1 high setpoint too high.
049
Channel 2 high setpoint too high.
050
Channel 3 high setpoint too high.
051
Channel 4 high setpoint too high.
The Peak tonnage high setpoint of the channel
indicated by the error code is set to a value
greater than 125% of the channel rating.
1)
Check the MACH RATING setting in the Config menu
for correctness.
2)
Adjust the indicated setpoint to a setting less
than 125% of the channel rating.
052
Channel 1 low setpoint too high.
053
Channel 2 low setpoint too high.
054
Channel 3 low setpoint too high.
055
Channel 4 low setpoint too high.
The Peak tonnage low setpoint of the channel
indicated by the error code is set to a value
greater than 125% of the channel rating.
1)
Check the MACH RATING setting in the Config menu
for correctness.
2)
Adjust the indicated setpoint to a setting less
than 125% of the channel rating.
056
Channel 1 reverse setpoint too high.
057
Channel 2 reverse setpoint too high.
058
Channel 3 reverse setpoint too high.
059
Channel 4 reverse setpoint too high.
The Peak tonnage reverse setpoint of the channel
indicated by the error code is set to a value
greater than 125% of the channel rating.
1)
Check the MACH RATING setting in the Config menu
for correctness.
2)
Adjust the indicated setpoint to a setting less