Kipp&Zonen LOGBOX SD Data Logger User Manual

Page 43

background image




43

Assign for A[X] 24 bit resolution

A[X]WI (X represents analog input. X [1...8])
Assign for A[X] 12 bit resolution

A[X]IS

(X represents analog input. X [1...5])

Set A[X] for single ended input. Only for 24 bit resolution

A[X]ID (X represents analog input. X [1...3])
Set A[X] for differential input. Only for 24 bit resolution

A[X]IU (X represents analog input. X [1...5])
Set A[X] for unipolar input. Only for 24 bit resolution

A[X]IB (X represents analog input. X [1...5])
Set A[X] for bipolar input. Only for 24 bit resolution

A[X]G[Y]

(X represents analog input, Y represents input range. X [1...5], Y[0...8])

Set A[X] for Y input range as follows:

Y

Input range

1

2.5V

2

1.25V

3

625mV

4

312mV

5

156mV

6

78mV

7

39mV

8

19mV



A[X]P[Y] (X represents analog input, Y represents nr. of polynomial. X [1...8], Y[0...8])
Set polynomial coefficients of P[Y] to analog input A[X]
If Y=0, no polynomial is used

Digital inputs configuration commands

BE
Clear all settings for bipolar inputs

B[X]C1 (X represent digital input. X [1...4])
Enable digital input X for counter function

B[X]C0 (X represent digital input. X [1...4])
Disable digital input X for counter function

B[X]F1 (X represent digital input. X [1...4])
Enable digital input X for frequency function

B[X]F0 (X represent digital input. X [1...4])
Disable digital input X for frequency function

B[X]P[Y] (X represents digital input, Y represents nr. of polynomial. X [1...4], Y[0...8])
Set polynomial coefficient of P[Y] to digital input B[X]
If Y=0, no polynomial is used

Polynomial coefficients configuration commands

PE
Clear all settings for polynomial coefficient