Automatic emergency announcement broadcasts – Toa VM-3000 Series User Manual
Page 39
39
Step 1. Press the RM-300MF’s Emergency Activation switch.
The Emergency indicator (Emergency Activation switch) lights red, placing the unit in emergency
broadcast mode.
Step 2. Press the RM-320F Fireman’s Microphone Extension’s Zone Selector key(s) to select broadcast
zone(s).
The selected zone’s indicator lights green, indicating that emergency microphone announcements
can be broadcast over the selected zone.
Notes
•
The RM-320F Fireman’s Microphone Extension is an optional device. If the Expansion Unit is not
connected, emergency announcements are broadcasts over all broadcast zones.
•
Use the setting software to set the Zone Selector key. (Refer to "Emergency Control Input Settings" in
"Event Settings" in the separate software instruction manual.)
•
If Step 2 is skipped and the broadcast zone is not selected, emergency announcements are broadcast over
all broadcast zones.
Step 3. Press either the RM-300MF’s Alert or Evacuation Announcement Start key.
The Alert Announcement indicator or Evacuation Announcement indicator and the RM-320F
Fireman’s Microphone Extension’s Emergency Output indicator both light red, broadcasting the Alert
or Evacuation announcement over the selected broadcast zone(s).
Note
Holding down the Alert Announcement Start key during Alert announcements or the Evacuation
Announcement Start key during Evacuation announcements for 3 seconds or more causes the announcement
to be terminated and the indicator to go out.
[RM-320F]
[RM-300MF]
Emergency Activation switch/Emergency indicator
Zone Selector key
Zone indicator
Emergency Broadcast
Zone indicator
Evacuation Announcement
indicator
Evacuation Announcement
Start key
Alert Announcement
indicator
Alert Announcement Start key
6.2.2. Automatic emergency announcement broadcasts
This function makes emergency broadcasts from the RM-300MF Fireman’s Microphone by playing back the
Alert or Evacuation announcements stored in the VM-3360VA or VM-3240VA.