beautypg.com

1 uncrating and inspecting, 2 preparing the heater for installation, 1 general (cont'd) – Reznor B Unit Installation Manual User Manual

Page 4

background image

Form I-F/B, P/N 98126 R21, Page 4

When units are located in the center of the space to be heated, the air should be dis-

charged toward the exposed walls. In large areas, units should be located to discharge

air along exposed walls with extra units provided to discharge air in toward the center

of the area.
At those points where infiltration of cold air is excessive, such as at entrance doors and

shipping doors, it is desirable to locate the unit so that it will discharge directly toward

the source of cold air from a distance of 15 to 20 feet (4.6-6.1M).
Units should not be installed closer than 18 inches (457mm) from any wall.

CAUTION: Do not locate the heater where it may be exposed

to water spray, rain or dripping water.

2. Unit Heater

Location

(cont'd)

3. Uncrating and

Preparation

3.1 Uncrating and Inspecting

This unit was test operated and inspected at the factory prior to crating and was in

operating condition. If the heater has incurred any damage in shipment, document the

damage with the transporting agency and immediately contact your Reznor Distribu-

tor.
Check the rating plate for the gas specifications and electrical characteristics of the

heater to be sure that they are compatible with the gas and electric supplies at the

installation site.

3.2 Preparing the Heater for Installation

Read this booklet and become familiar with the installation requirements of your par-

ticular heater. If you do not have knowledge of local requirements, check with the local

gas company or any other local agencies who might have requirements concerning

this installation. Before beginning, make preparations for necessary supplies, tools,

and manpower.
Check to see if there are any field-installed options that need to be assembled to the

heater prior to installation. Each of the option packages includes a list of components

and step-by-step instructions. For a brief description of optional hanger kits, refer to

Paragraph 5.2.1. Other option kits that should be installed prior to installation include

louvers, nozzle kits, polytube adapter, duct flange, guards, vent damper, power ven-

2.2 Combustion Air

Requirements

for a Heater

Located in a

Confined Space

Do not install a unit in a confined space without providing wall openings leading to and

from the space. Provide openings near the floor and ceiling for ventilation and air for

combustion as shown in

FIGURE 1, depending on the combustion air source as noted

in Items 1, 2, and 3 below the illustration.
Add total BTUH of all appliances in the confined space and divide by figures below for

square inch free area size of each (top and bottom) opening.
1. Air from inside the building -- openings 1 square inch free area per 1000 BTUH.

Never less than 100 square inches free area for each opening. See (1) in

FIGURE 1.

2. Air from outside through duct -- openings 1 square inch free area per 2000

BTUH. See (2) in

FIGURE 1.

3. Air direct from outside -- openings 1 square inch free area per 4000 BTUH. See

(3) in

FIGURE 1.

FIGURE 1 - Confined

Space: A space whose

volume is less than

50 cubic feet per 1000

BTUH of the installed

appliance input rating

(3)

(3)

(1)

(1)

(2)

(2)

Confined

Space

2.1 General (cont'd)

NOTE: For further details on supplying combustion air to a confined space, see the

National Fuel Gas Code ANSI Z223.1a (latest edition ).

This manual is related to the following products: