Form I-F/B, P/N 98126 R21, Page 25

Multiple Heater Control - These unit heaters are not designed for multiple unit connection to one thermostat.

If you require that more than one unit be controlled by a single thermostat, it will be

necessary to use relays in the circuit. Options CL31 and CL32 provide the necessary

parts and instructions for multiple heater control.
The multiple heater control options are designed to permit the control of up to six heat-

ers with a single thermostat or time clock and single/multiple thermostats.
For maximum safety, the multiple control is in the low voltage circuit. These multiple

heater control options may not be used with two-stage gas valves.

When factory-installed options require two-stage thermostat control, the heater is

equipped with a SP-ST relay and a four-screw terminal connector strip (See

FIGURE

27).
If your heater requires field installation of the four-screw terminal strip and the relay,

follow the instructions packaged with the relay or thermostat option.

FIGURE 28 illus-

trates the wiring and the connections required for an optional field-installed fan relay.

Two Screw

Terminal Connector

Strip

FIGURE 26 -

Two Screw

Terminal Connector Strip for

24-Volt Wiring

FIGURE 27 - Optional

Four Screw Terminal

Connector Strip for 24-Volt

Wiring

Optional

Four

Screw Terminal

Connector Strip

FIGURE 28 - Wiring Diagrams for Field-Installed Fan Relay (Option CL21)

575/3/60

FIGURE 29 - Wiring

Label for Multiple

Heater Control Wiring

with Options CL31 and/

or CL32