beautypg.com

3 inlet air - blower model b, 3 vent control damper, option av7, 4 optional power venting - option ca – Reznor B Unit Installation Manual User Manual

Page 19

background image

Form I-F/B, P/N 98126 R21, Page 19

6.2.3 Vent Control

Damper, Option AV7

The vent damper option is a motorized damper that

will close when the heater is not operating. The vent

damper is applicable only with spark ignition with

lockout (Control Option AH3). See

NOTES below

and follow the manufacturer's instructions to install it

in the vent. See the wiring diagram on the heater to

make the wiring connections.

NOTES: The wiring harness with the vent damper

is 8 ft (2.4M) in length. The vent damper should be

located as close to the heater as possible and cannot

FIGURE 17 - Option AV7,

Vent Control Damper

NOTE: A gravity-vented

unit heater manufactured

after August 7, 2008, MUST

be installed with either an

automatically controlled

motorized vent damper

(Option AV7) or power

venting (Option CA).

6.2.4 Optional Power

Venting - Option CA

Option CA is a motorized vent exhauster that is designed to permit the operation of

these gravity-vented heaters in areas of negative pressure up to 0.15" w.c. or where

horizontal venting is required.

NOTE: Do not install an

Option CA venter on a

heater equipped with

voltage option AK11,

220-240/1/50 Hertz.

The option package includes complete installation and wiring instructions. The venter

is wired so that when the thermostat calls for heat, the thermostat contacts close the

circuit which, after a delay of approximately 30 seconds, starts the venter. When the

venter starts, air from the venter blower closes an air flow switch that is built into the

venter. The closing of the air flow switch completes the electric circuit to the burner con-

trols, opening the gas valve. When the thermostat is satisfied, the thermostat closes

the gas valve and de-energizes the time delay relay. Approximately 45 seconds after

the thermostat is satisfied, the air flow switch resets to the open position.
The addition of the optional power venter changes the vent size requirements

of the heater. The vent sizes and allowable vent lengths are listed in the installation

instructions in the option package.

FIGURE 18 - Venter

Assembly and Adapter

The option package also includes

two hanger brackets to convert a fan-

type heater to four-point suspension.

Four-point suspension is required to

maintain the unit in a level position

without putting stress on the gas valve

or piping.

6.3 Inlet Air - Blower

Model B

FIGURE 19 - Optional

Field-Installed Blower/

Filter Cabinet

Blower Cabinet with Filters

(Option CW2 or CW3) -- side

panel removed to illustrate

interior of cabinet

Blower Cabinet

without filters (Option CW1)

6.3.1 Optional Blower/Filter Cabinet - Options CW1, CW2, or CW3

(Blower Models Only)

The blower/filter cabinet option is available for all Model B sizes. The blower/filter cabi-

net is shipped separately for field assembly and installation. The cabinet is adaptable

for use with either 1" or 2" filters and may be connected to a return air duct (includes

3/4" duct flange). Option CW1 does not include filters; CW2 includes 1" permanent

aluminum filters; and CW3 includes 2" permanent aluminum filters.
Follow the illustrated instructions included with the option package.

Model

Size

Qty

Filter

Size

Replacement P/N

1" Filter 2" Filter

25-125

1

20 x 20

101608

101621

165-200

1

16 x 25

101609

101622

1

20 x 25

101610

101623

250-300

2

16 x 20

101607

101620

2

20 x 20

101608

101621

400

2

16 x 25

101609

101622

2

20 x 25

101610

101623

be more than 8 ft (2.4M) from the ignition controller. The ignition controller has a safety

feature that once it is used with a vent damper, it will no longer operate a unit without

a vent damper.

This manual is related to the following products: