HARDWIRE DETECTION ADDER MODULE (ZA-9008)

-

8 supervised Style B (Class B) or 4 Style D (Class A) Initiating Circuits; fully configurable. Terminals are labeled “INI”.

Initiating Circuits are Compatibility ID “A”.

Power Limited: 22VDC, 3 mA standby, 5mV ripple, 50 mA max. (alarm)

-

Current Consumption: Standby: 80 mA, Alarm: 100 mA

HARDWIRE SIGNAL ADDER MODULE (IDC-9004)

-

4 Style Y or Z (Class B or A) Notification Circuits; configurable as strobes or audibles.

Terminals are labeled “IND”.

Power Limited: 24 VDC unfiltered 1.25 A @ 49°C per Circuit

-

Current Consumption: Standby: 35 mA, Alarm: 150 mA

HARDWIRE RELAY ADDER MODULE (ARM-9008) (resistive loads)

-

Must be connected to a Listed Power Limited Source of Supply. Terminals are labeled “RLY”.

-

8 fully Configurable Form C Relays.

Form C, 1 Amp., 28 VDC (resistive loads)

-

Current Consumption: Standby: 25 mA, Alarm: 150 mA

POLARITY REVERSAL AND CITY TIE MODULE (PR-5000)

-

Supervised City Tie Not Power Limited

24VDC unfiltered, 210 mA max., Trip coil: 14 ohms.

Terminals are labeled “City Tie”.

-

Polarity Reversal Power Limited

Terminals are labeled “Polarity Reversal”.

24VDC open

12VDC @ 3.5 mA, 8 mA max. (shorted)

-

Current Consumption: Standby: 35 mA, Alarm: 300 mA

System Model:

SERIES PFC-9000, Fire Alarm Control Panel

System Type:

Local, Auxiliary (using PR-5000), Remote Protected Premise Station (using PR-5000 or

UDACT-9100), Central Station Protected Premises (using DACT-5000 or UDACT-9100)

Type of Service:

A, M, WF, SS (with UDACT-9100)

Type of Signalling: Non-Coded

Applicable Standards:

NFPA 70 and 72, UL-864, ULC S-524, ULC S-527.