HARDWIRE DETECTION ADDER MODULE (ZA-9008)
-
8 supervised Style B (Class B) or 4 Style D (Class A) Initiating Circuits; fully configurable. Terminals are labeled “INI”.
Initiating Circuits are Compatibility ID “A”.
Power Limited: 22VDC, 3 mA standby, 5mV ripple, 50 mA max. (alarm)
-
Current Consumption: Standby: 80 mA, Alarm: 100 mA
HARDWIRE SIGNAL ADDER MODULE (IDC-9004)
-
4 Style Y or Z (Class B or A) Notification Circuits; configurable as strobes or audibles.
Terminals are labeled “IND”.
Power Limited: 24 VDC unfiltered 1.25 A @ 49°C per Circuit
-
Current Consumption: Standby: 35 mA, Alarm: 150 mA
HARDWIRE RELAY ADDER MODULE (ARM-9008) (resistive loads)
-
Must be connected to a Listed Power Limited Source of Supply. Terminals are labeled “RLY”.
-
8 fully Configurable Form C Relays.
Form C, 1 Amp., 28 VDC (resistive loads)
-
Current Consumption: Standby: 25 mA, Alarm: 150 mA
POLARITY REVERSAL AND CITY TIE MODULE (PR-5000)
-
Supervised City Tie Not Power Limited
24VDC unfiltered, 210 mA max., Trip coil: 14 ohms.
Terminals are labeled “City Tie”.
-
Polarity Reversal Power Limited
Terminals are labeled “Polarity Reversal”.
24VDC open
12VDC @ 3.5 mA, 8 mA max. (shorted)
-
Current Consumption: Standby: 35 mA, Alarm: 300 mA
System Model:
SERIES PFC-9000, Fire Alarm Control Panel
System Type:
Local, Auxiliary (using PR-5000), Remote Protected Premise Station (using PR-5000 or
UDACT-9100), Central Station Protected Premises (using DACT-5000 or UDACT-9100)
Type of Service:
A, M, WF, SS (with UDACT-9100)
Type of Signalling: Non-Coded
Applicable Standards:
NFPA 70 and 72, UL-864, ULC S-524, ULC S-527.