IDC-9004 4 Zone Notification Circuit Adder Card

The IDC-9004 provides four additional zones of Class A (Style Z) or Class B (Style Y) notification circuits. The IDC-9004 is

programmed in the configuration software as either a strobe or signal circuit. When programmed as a signal circuit, that circuit

will operate at the same rate as programmed in the configuration software.
Each circuit of the IDC-9004 are power limited and have a maximum of 1.7 Amps. Each circuit can be programmed to be

silenceable (deactivated) or nonsilenceable. All terminals are removeable for easy wiring.

Jumpers
JW1

Continuity Jumper installed only if device is the last circuit adder installed

JW2

Jumper for ability to deactivate the bells on Circuit 1

JW3

Jumper for ability to deactivate the bells on Circuit 2

JW4

Jumper for ability to deactivate the bells on Circuit 3

JW5

Jumper for ability to deactivate the bells on Circuit 4

JW11 Terminals for Bell Cut Relay

Plugs
P1

Data cable for next circuit adder

P2

Data cable attached to previous circuit adder or main fire alarm

P3

Power connector to next circuit adder

P4

Power connector to P8 of fire alarm board or previous circuit adder module

FIELD

WIRING

TERMINAL

S

JW5

JW4

JW3

JW2

JW1

P1

P3

P2

P4

JW11

DWG# PFC-9000-18

Failure to connect notification circuits to notification appliances will result in occupants not being notified to evacuate or relocate.