Potter PFC-9000 Series User Manual
Page 28
28
PFC-9000 • 5403535 • REV G • 9/08
IDC-9004 4 Zone Notification Circuit Adder Card
The IDC-9004 provides four additional zones of Class A (Style Z) or Class B (Style Y) notification circuits. The IDC-9004 is
programmed in the configuration software as either a strobe or signal circuit. When programmed as a signal circuit, that circuit
will operate at the same rate as programmed in the configuration software.
Each circuit of the IDC-9004 are power limited and have a maximum of 1.7 Amps. Each circuit can be programmed to be
silenceable (deactivated) or nonsilenceable. All terminals are removeable for easy wiring.
Jumpers
JW1
Continuity Jumper installed only if device is the last circuit adder installed
JW2
Jumper for ability to deactivate the bells on Circuit 1
JW3
Jumper for ability to deactivate the bells on Circuit 2
JW4
Jumper for ability to deactivate the bells on Circuit 3
JW5
Jumper for ability to deactivate the bells on Circuit 4
JW11 Terminals for Bell Cut Relay
Plugs
P1
Data cable for next circuit adder
P2
Data cable attached to previous circuit adder or main fire alarm
P3
Power connector to next circuit adder
P4
Power connector to P8 of fire alarm board or previous circuit adder module
FIELD
WIRING
TERMINAL
S
JW5
JW4
JW3
JW2
JW1
P1
P3
P2
P4
JW11
DWG# PFC-9000-18
Failure to connect notification circuits to notification appliances will result in occupants not being notified to evacuate or relocate.