Pfc-9000 fire alarm main board connections – Potter PFC-9000 Series User Manual
Page 10
10
PFC-9000 • 5403535 • REV G • 9/08
PFC-9000 Fire Alarm Main Board Connections
Jumpers
JW 1 - Used when a PR-5000 or UDACT-9100 is installed. Remove the jumper any time one of these devices is added.
JW 2 - For factory programming only, not for field use, DO NOT MODIFY
JW 3 - For factory programming only, not for field use, DO NOT MODIFY
JW 4 - For factory programming only, not for field use, DO NOT MODIFY
Plug Connections
P1
-
Not Used
P2
-
RS-485 connection for computer programming connection
P3
-
Not Used
P4
-
Port for connecting PR-5000 or UDACT-9100
P5
-
Loop Adder connection port
P6
-
Circuit adder card communication connection
P7
-
Factory use only
P8
-
Power connection for adder cards
P9
-
RS-232 connection for printer or CRT
P10&11 -
Power connection to bridge rectifer
P12&13 -
Connection for 24VDC batteries
P14
-
Connection for LCD display board
F1 – 20 Amp AGC or equivalent battery fuse
P1
P2
FIELD WIRING TERMINALS
P3
P5
P6
P8
P4
JW1
P14
JW3
JW2
JW4
P7
P9
P10 P11 +BDG-
P12 P13 +BDG-
MAIN FIRE ALARM BOARD
DWG# PFC-9000-13
F1