beautypg.com

Indicators, controls, & operation – Potter PFC-9000 Series User Manual

Page 7

background image

7

PFC-9000 • 5403535 • REV G • 9/08

INDICATORS, CONTROLS, & OPERATION

Note: The two Programmable Buttons, General Alarm, and Acknowledge buttons are not labeled. Slide labels are provided in the

event these buttons are used.
The main display for the PFC-9000 Series Fire Alarm Panel consist of a four-line, twenty character liquid crystal display (LCD)

that interfaces with the user to operate, program and diagnose the panel. The LCD will display information from each of the

queues as well as reporting and programming messages.
The panel has four queues where the different inputs are grouped based on the type. The queues are ALARM, SUPV

(supervisory), TROUBLE and MONITOR and the information of the status of the panel and devices will fall under one of the

queues. Each queue has an associated LED with it. The PFC-9000 will illuminate a red LED only when an alarm condition is

present. All other conditions including ground fault, supervisory and trouble conditions will be visually indicated on the panel

with a yellow (amber) LED and a corresponding message on the LCD screen.
The PFC-9000 panel has six buttons that control basic operations of the panel. Two of these buttons are programmable in the

computer software and the others are standard. The standard buttons are SYSTEM RESET, SIGNAL SILENCE, FIRE DRILL and

LAMP TEST.
The SYSTEM RESET is used to restart the panel after initial power up and used to reset any alarm condition or latching

supervisory condition. The System Reset will turn off the Fire Drill, reset 4-wire smoke power, reset timers and begin to process

inputs as new events. The SYSTEM RESET will also clear any Pre-alarm condition that exists on the panel. When the system is

restarted and reset, a time and date stamp is logged in the Alarm and Event history buffer.
The SIGNAL SILENCE is used to silence/deactivate the notification circuits that are programmed as silencable/deactivate

capable. Upon receipt of subsequent alarms, the silenced/deactivated circuits will be reactivated. If the Signal Silence Inhibit is

programmed, the Signal Silence will not operate until the timer has expired. In Two Stage operations, if the Auto General Timer

has timed out, the Signal Silence will operate the same as the Acknowledge button.

POTTER PFC-9000

FIRE ALARM CONTROL PANEL

NORMAL CONDITION

JANUARY 1, 2008

ENTER

MENU

CANCEL

INFO

ALARM

QUEUE

SUPV

QUEUE

TROUBLE

QUEUE

LAMP TEST

A.C. ON

PRE-ALARM

GND FAULT

SYSTEM

RESET

SIGNAL

SILENCE

FIRE

DRILL

ALARM

QUEUE

PROGRAM-

MABLE

BUTTON

PROGRAM-

MABLE

BUTTON

GENERAL

ALARM

ACKNOWL-

EDGE

DWG# PFC-9000-4

Do not silence the system prior to investigating source of the alarm. All occupants may not have evacuated if the system is

silenced prematurely.