beautypg.com

Potter PFC-9000 Series User Manual

Page 40

background image

40

PFC-9000 • 5403535 • REV G • 9/08

ADSD Duct Smoke Detector

The ADSD is the duct smoke detector designed to easily mount on the side of an HVAC duct and monitor for smoke conditions

in the duct. A template and mounting hardware is provided with the unit for mounting. The device mounts without the removal of

the outer cover. The devices are designed to operate without screens and filters, therefore the amount of maintenance needed for

the device is minimal. The fire alarm panel controls the sensitivity of the smoke sensor.
Both the ADSD-P and ADSD-PR utilize a photoelectric smoke sensor. The ADSD-P has four terminals, two for the SLC loop and

two for remote output of an LED. The ADSD-PR has terminals for two form C relays that are rated for 10 amps at 125/250 VAC.

The ADSD-PR requires 24 VDC to operate. Failure to provide 24 VDC power will result in the panel showing a missing device.

The ADSD will monitor airflow between 300 and 4,000 feet per minute and require that the user purchase air-sampling tubes in

order to achieve proper airflow through the unit. Sampling tubes are available in 3, 5 and 10-foot lengths.

THE ADSD-P AND ADSD-PR ARE NOT SELF-

CONTAINED SENSORS. THIS PRODUCT IS

COMPATIBLE ONLY WITH FIRE ALARM

CONTROL PANELS THAT UTILIZE HOCHIKI’S

DIGITAL COMMUNICATIONS PROTOCOL,

DCP. FOR EXAMPLE, THE POTTER PFC-9000.

ADSD-P

REMOTE LED WIRING MUST

HAVE POLARITY AS SHOWN

(24 VDC 8mA MAX)

S

SC

UL

LISTED

CONTROL

P

ANE

L

LOOP

INTERF

ACE

TO

NEXT

SENSOR

DWG# PFC-9000-26A

L1

L2

L3

L4

1

2

3

4

ADSD-P Wiring Diagram

The ADSD is addressed in one of two ways and both require the removal of the cover to access the smoke head. The head can be

removed and inserted on the hand held programmer and addressed like all of the other sensors. The other option is to use the FRCM-2

cable and connect to the SLC terminal strip on the ADSD. The programming of the device is the same as if it was connected.

ADSD-PR Wiring Diagram

UL

LISTED

CONTRO

L

PANE

L

ADDRESSABLE

LOOP

OBSERVE POLARITY

INPUT VOLTAGE 24 VDC 10mA

STANDBY 55mA ALARM

REMOTE

ALARM

LED

SUPPLY VOLTAGE

FAN

ALARM CONTACTS 10A

NO

C

NC

NO

C

NC

ALARM CONTACTS 10A

TO NEXT SENSOR OR

RETURN TO CONTROL

PANEL

ANALOG ADDRESSABLE FIELD

LOOP WIRING

TERMINATE REMOTE ACCESSORIES AS INDICATED ABOVE (IF REQUIRED). THIS IS NOT A

SELF-CONTAINED STAND ALONE DETECTOR. A UL LISTED ANALOG ADDRESSABLE FIRE

SYSTEM IS REQUIRED.

DWG# PFC-9000-26B

REMOTE

PILOT LED

REMOTE

TEST

SWITCH

LOOP

INTER

FA

CE

S

SC

1

2

3

4

5

6

7

8

9

10

11

12