Clear Event Log
This control allows the user to select the log that they wish to clear: Alarm, Event or All. Select the Clear Event Log and enter the
pass code if necessary.
- Select Log -
1 Alarm Log
2 Event Log
3 All Logs
Once the log is selected push the ENTER button. The panel will query the user to verify that they want to clear that log. If you are
sure, push the ENTER button, if not push the CANCEL button.
Clear Verification Count
The Clear Verification Count clears the log of the verified alarms received. The Clear Verification Count may require a pass code
if one is installed.
Auto Program
Once all of the devices have been uniquely addressed and installed, the user can utilize the Auto Program feature to quickly
program all of the devices into the panel, or when new devices are added to the system they can quickly be added. In addition,
the Auto Program creates a fail-safe system in which every new input is configured as an alarm input and they are automatically
correlated to every output including notification circuits and the alarm relay. The panel can be auto programmed and then the
program downloaded to a computer for device mapping and sensor adjustment.
The Auto Program feature will not program the annunciators into the system. The annunciators must be programmed using the
computer software. If the panel has a trouble that includes an annunciator with a data link trouble or version mismatch, the Auto
Program will abort.
Potter strongly recommends that the Auto Program feature have at least a level 2 pass code protection.
Press the button, the display will read
-Command Menu-
1 Reports
2 Bypass
3 Walktest v
Press the Scroll Up arrow until #9 “Autoprogram”
Press the button, the display will ask for a passcode of level 2 or higher. The factory default
passcode is 2222 which is the TROUBLE QUEUE button four times.
The display will indicate X number of new devices found on loop Y, add with default programming? Y
Press the button.
The display will read WARNING System must be Thoroughly Rechecked When Done, Continue? Y
Press the button.
The display will indicate that autoprogramming is in process.
NOTE: When the panel is finished all addressable modules that have been added to the panel through the autoprogram feature
default to a general alarm signal and are automatically mapped to all notification circuits.
MENU
ENTER
ENTER
ENTER