beautypg.com

Potter PFC-9000 Series User Manual

Page 14

background image

14

PFC-9000 • 5403535 • REV G • 9/08

Electrical Specifications

Input Power

The PFC-9000 operates on a nominal 120 or 240 VAC with a minimum and maximum line voltage of 102 VAC and 132 VAC

or 204 VAC and 264 VAC respectively. A resettable 4-Amp fuse is installed on the primary side of the transformer-input power.

The transformer is a 24-volt transformer that provides 12 Amps of power to the panel. For more detailed information on power

consumption refer to the battery calculation sheet.
The fire alarm panel must be connected to a dedicated circuit and should be wired using 12 AWG wire through the side conduit

entrance. The black (hot) must be connected to the line, the white to the neutral (N) and the green to the ground. An earth ground

must also be connected to the cabinet.

Battery Backup Requirement

The PFC-9000 is capable of charging standby batteries from 17 to 40 amp-hours. The batteries should be sized according to the

battery calculation performed that accounts for all standby currents and power requirements when the panel is in alarm.

When the panel communicates to a Central Station, a minimum of 24 hours of stand-by current and five minutes of alarm current

is required. When communicating to a Remote Supervising Station, a minimum of 24 hours of battery stand-by is required

followed by five minutes of alarm current.
The cabinet will house up to 18 amp-hour batteries; larger batteries will need to be housed in a separate cabinet.
A 20-amp fuse on the main board protects the battery circuit. If the panel is showing a trouble condition of missing batteries, and

the batteries are connected and meter to the correct voltages, then the fuse should be replaced.

Per the National Electrical Code, the fire alarm circuit breaker should be marked red and labeled.

Permanent installations require AC power and battery backup to be supplied to the panel. Failure to properly size batteries

could result in the panel prematurely shutting down when there is a loss of AC power.
17 AH batteries are the minimum capacity batteries allowed in the PFC-9000 series. The installation of batteries with a

capacity less than 17 AH will damage the batteries and panel.

Connect AC power to panel followed by batteries. Observe polarity when connecting batteries. Failure to do so may result

in damage to the batteries, battery leads, or panel.