Programming A/A Modules

The FRCM-4, SOM and DRM utilize a remote programming cable that plugs into the module. The cable plug is marked

with a number 1 and that must coincide with the plug 1 on the module. The FRCM-2 utilizes the cable without the plug for

programming. When programming the modules, at least one of the SLC wires must be removed.
To program modules, the device must be isolated from the loop by removing at least one of the SLC loop wires. The TCH-

B100 has a programming jack that the remote cable is plugged into for programming the modules. Powering the unit up and
programming is identical for the sensors.

SLC Analog Device Wiring
AIS, APS, AHD, Smoke Sensors, and Heat Detectors

All of the sensors are essentially wired the same way. The AIS, APS and AHD sensors must be connected to an ABS-6 or

equivalent base. The base must be secured to a back box and all of the field wiring is connected to the base.

DWG# PFC-9000-23

ASB-6 BASE