Potter PFC-9000 Series User Manual
Page 26
26
PFC-9000 • 5403535 • REV G • 9/08
ZA-9008 Conventional Circuits Card
The ZA-9008 provides either eight Class B conventional circuits or four Class A conventional circuits in addition to the addresses
on the loop. The zones may be selected as a number of different input types as allowed in the Configuration Software. Any of the
conventional inputs may be correlated to any of the outputs. All field-wiring terminals are removeable for ease of wiring. The ZA-
9008 can be installed on top of the UDACT-9100 card in the left space, or in any available space from right to left.
The list for compatible devices is in Appendix C.
Jumpers
JW1
Jumper installed for Class A (Style D) initiation of Circuits 1 & 2
JW2
Jumper installed for Class A (Style D) initiation of Circuits 3 & 4
JW3
Jumper installed for Class A (Style D) initiation of Circuits 5 & 6
JW4
Jumper installed for Class A (Style D) initiation of Circuits 7 & 8
JW5
Continuity Jumper installed only if device is the last circuit adder installed
Plugs
P1
Data cable for next circuit adder
P2
Data cable attached to previous circuit adder or main fire alarm
P3
Power connector to next circuit adder
P4
Power connector to P8 of fire alarm board or previous circuit adder module
FIELD
WIRING
TERMINAL
S
JW4
JW3
JW2
JW1
JW5
P1
P3
P2
P4
DWG# PFC-9000-17
Failure to use tested and listed compatible powered devices may result in system not operating or false activations.