Potter PFC-9000 Series User Manual
Page 76
76
PFC-9000 • 5403535 • REV G • 9/08
DWG. #PFC-9000-43
IN-B
IN-A
SC-
SC+
NO 1
COM 1
NC 1
NO 2
COM 2
NC 2
SC (OUT)
S (OUT)
SC (IN)
S (IN)
CONNECT
TO FAN
SHUTDOWN
CIRCUIT
FAN RE-START SWITCH
FRCM
DRM-4
Test Menu
The Test Menu allows the user to transfer the entire database as well as validate the entire database with a single command. The
Extract All Db allows the user to copy the entire database and transfer it to a multimedia device or another drive. The Validate All
will validate every job and every version that is currently in the software. Depending on the size of the database, the Validate All
command could require a substantial amount of time.
The Log Send, Log Get and Trace are future commands that are not currently available.
View Menu
The View Menu enables the tool bar at the top of the page and the status bar at the lower part of the page. The tool bar contains all
of the common file commands such as create a new job, open an existing job, cut, copy, paste and print reports. The other buttons
are shortcuts for connecting to the panel, sending jobs to the panel and getting jobs from the panel.
Help Menu
There is currently not a written help menu for the PFC Config program. The help menu under the About PFC Config will give the
version of the software and when it was installed.
Fan shutdown/Restart
Equipment required:
Qty. Model #. Description
1 DRM-4
Dual relay module
1 FRCM
Fast Response
Contact Module
1
Fan Re-start switch
Wiring Procedure
Connect DRM-4 to loop.
Connect relay #1 of DRM to fan shutdown circuit.
Connect N.O. #2 of DRM to the N.C. contact of the Fan Re-start switch
The Common of the Re-start switch is connected to IN-B of the FRCM-2.
Connect COM #2 of DRM to the IN-A terminal of the FRCM-2.
Connect FRCM-2 to the loop
Programming Information
Correlate the devices that will be used to shut down the fan to the DRM-4.
Program FRCM-2 a monitor point
Correlate the FRCM-2 to the DRM-4.