Potter PFC-9000 Series User Manual
Page 60
60
PFC-9000 • 5403535 • REV G • 9/08
Print Reports - Input Messages
From the previous screen, double clicking on the version of the report selected will bring up the input message screen shown below.
The reports include input to output correlations, input message tags, duplicate inputs and outputs and UDACT-9100 mapping.
Below is a description of the various buttons and columns on the screen.
•
The Print button prints the current screen
•
The Preview button displays how the report will look
•
The Close button will close that particular report and return to the section displaying the various jobs with the
job versions
•
The Dup Inputs and Dup Outputs are devices that have been programmed with duplicate addresses. Similarly,
the Dup inputs show the duplicate inputs and the outputs that are correlated to them.
•
The input message gives the messages of the inputs in the system
•
LED Groups displays the correlation of the LED’s on the LED annunciator adders
•
CPU No column refers to the internal process address in the system. CPU No. 0 is the main fire alarm panel.
CPU No. 33 is an RA-LCD annunciator.
•
Ckt No is the circuit number for the internal addressing in the system. The panel selects the circuit number
automatically and chronologically in the order that the equipment was entered into the configuration software.
The circuit numbers start at number 0.
•
LoopNo is the Loop Number as described earlier
•
DevAddr is the address for the device
•
SYSDev Types tag is the type of device the address is assigned to such as Hochiki Ion
•
SYSProc Types tag is the type of signal an address is programmed to send to the panel such as Alarm