beautypg.com

Potter PFC-9000 Series User Manual

Page 35

background image

35

PFC-9000 • 5403535 • REV G • 9/08

SLC Wiring Styles

The National Fire Code defines the minimum requirements for Signaling Line Circuits and the respective operating parameters

with a fault condition. Consult the local AHJ to determine which class and style of wiring is required.

Class B (Style 4) Addressable Loop Wire Terminations

SLC LOOP

CLASS B

4W SUP AUX PWR

AUX. POWER

24 VDC UNFILTERED, 1.7 MAX

CLASS B USE LEFT

POSITIVE AND NEGATIVE

PFC-9000

FACP

127 DEVICES PER LOOP, ANY

COMBINATION OF SENSORS

AND MODULES

A MAX. OF 50 DEVICES PER T-TAP

UP TO 10 OHMS PER T-TAP

50 OHMS TOTAL RESISTANCE ON

SLC LOOP INCLUDING T-TAPS

(30,000 FEET 12 AWG CABLE)

KEY

SMOKE OR HEAT SENSOR

PSCI ISOLATOR

DWG# PFC-9000-35