Potter PFC-9000 Series User Manual
Page 39
39
PFC-9000 • 5403535 • REV G • 9/08
The SLC loop, the sensors and the bases are polarity sensitive. The panel will have the terminals marked for positive and negative
for both Class A and Class B. The base has three sets of terminals. Terminals number 1 and 2 are for the positive, terminals 5 and
6 are for the negative and terminals 3 and 4 are for a remote annunciation. The remote annunciation has a maximum output of 8
mAmps per base.
UL LISTED
COMPATIBLE
CONTROL
PANEL
FOR REMOTE ANNUNCIATION IF USED
ASB-6
8mA MAX.
OUTPUT
DWG# PFC-9000-24
ASB-6
The sensors will only slide onto the base one way. The “DO NOT PAINT” that is embossed on the sensor should line to the right
of the Potter on the base and turn clockwise onto the base.
COVER
POTTER
LABEL
DWG# PFC-9000-25
DO
N
OT P
AIN
T