beautypg.com

App1, Appendix 1 - error codes (continued) – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 99

background image

89

Service Manual NeoTherm 80 - NeoTherm 285

Appendix 1 - Error Codes (continued)

Code Description

L or H Procedure

153

Combustion pressure off

H or L 1. Check wiring and correct any errors.

2. Inspect the combustion pressure switch to make sure

it is working correctly.
3. Reset and sequence the relay module.
4. During standyby and prepurge, measure the volt-

age between J6 terminal 5 and L2 (N). Supply voltage

should be present. If not, the lockout switch is defective

and needs replacing.
5. If the fault persists, replace the relay module.

154

Purge fan switch on

H or L 1. Purge fan switch is on when it should be off.

2. Check wiring and correct any errors.
3. Inspect the purge fan switch J6 terminal 3 and its

connections. Make sure the switch is working correctly

and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

155

Purge fan switch off

H or L 1. Purge fan switch is off when it should be on.

2. Check wiring and correct any errors.
3. Inspect the purge fan switch J6 terminal 3 and its

connections. Make sure the switch is working correctly

and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

156

Combustion pressure and flame on

H or L 1. Check that flame is not present in the combustion

chamber. Correct any errors.
2. Make sure that the flame detector is wired to the cor-

rect terminal.
3. Make sure the flame and ground wires are protected

from stray noise pickup.
4. Reset and sequence the module, if code reappears,

replace the flame detector.
5. Reset and sequence the module, if code reappears,

replace the module.

157

Combustion pressure and flame off

L

1. Check that flame is not present in the combustion

chamber. Correct any errors.
2. Make sure that the flame detector is wired to the cor-

rect terminal.
3. Make sure the F & G wires are protected from stray

noise pickup.
4. Reset and sequence the module, if code reappears,

replace the flame detector.
5. Reset and sequence the module, if code reappears,

replace the module.

158

Main valve on

L

1. Check the main valve terminal wiring and correct any

errors.
2. Reset and sequence the module. If fault persists,

replace the module.

App1

cont.

This manual is related to the following products: