beautypg.com

B5 - controller for low water cutoff, Controller for low water cutoff – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 29

background image

19

Service Manual NeoTherm 80 - NeoTherm 285

Checking the Low Water Cutoff Switch (continued)

Controller for Low Water Cutoff

The low water cutoff switch operates by passing

a slight electrical current between from a probe to

ground when water is surrounding the probe. If there

is no water, there is no current, and the controller

knows that the water level has dropped.
The low water cutoff controller is shown in Fig. B5-1

The controller has two LED indicators:
• Power (red) – When lighted, the control box has

power.

• Tripped (yellow) – When lighted, the controller

has detected a low water condition.

The controller also has two switches:
• Reset – Use this to cancel the “trip” condition.
• Test – This simulates a “low water” condition.
See “Removing and Replacing the Low Water Cutoff

Switch,” Section B6.

Fig. B5-1 - Controller for low water cutoff

Check for dirty probe.

Probe dirty?

Yes

Wipe down the probe.

(Do this once a year.)

System recently

installed?

Yes

Drain and flush the system.

No

The system may have tripped

because of small air bubbles.

B4

cont.

B5

This manual is related to the following products: