Appendix 1 - Error Codes (continued)

Code Description

L or H Procedure

97

Internal fault: A2D mismatch.

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

98

Internal fault: Exceeded VSNSR voltage

tolerance

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

99

Internal fault: Exceeded 28V voltage toler-

ance

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

100

Pressure sensor fault

H

1. Verify the pressure sensor is a 4-20 ma source.
2. Check wiring and correct any possible errors.
3. Test the pressure sensor for correct operation.
4. Replace the pressure sensor.
5. If previous steps are correct and fault persists, re-

place the module.

105

Flame detected out of sequence

H or L 1. Check that flame is not present in the combustion

chamber. Correct any errors.
2. Make sure that the flame detector is wired to the cor-

rect terminal.
3. Make sure the flame and ground wires are protected

from stray noise pickup.
4. Reset and sequence the module, if code reappears,

replace the flame detector.
5. Reset and sequence the module, if code reappears,

replace the module.

106

Flame lost in MFEP (Main Flame Establish-

ing Period)

L

1. Check main valve wiring and operation - correct any

errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector,

flame detector siting and flame rod position.
5. If steps 1 through 4 are correct and the fault persists,

replace the module.

107

Flame lost early in run

L

1. Check main valve wiring and operation - correct any

errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector,

flame detector siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists,

replace the module.