beautypg.com

Appendix 1 - error codes, Appendix, App1 error codes – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 91: App1

background image

81

Service Manual NeoTherm 80 - NeoTherm 285

App1

Appendix 1 - Error Codes

This table includes a listing of the faults that might be generated by the controllers, and displayed on the Operator Interface. Some

of these can be corrected by an installer changing a parameter, while other conditions are more complicated, and will require a

service technician.

The first column lists the code number that will appear at the beginning of the Lockout or Hold message in the orange bar at

the bottom of the screen. The second column lists the text as it will appear on the Operator Interface. The third column shows

whether the condition will cause a Hold, or Lockout, or both. The fourth column lists some suggestions for corrective action.

Code Description

L or H Procedure

1

Unconfigured safety data

L

1. New device, complete device configuration and

safety verification.
2. If fault repeats, replace module.

2

Waiting for safety
data verification

L

1. Device in Configuration mode and safety parameters

need verification and a device needs reset to complete

verification.
2. Configuration ended without verification, re- enter

configuration, verify safety parameters and reset device

to complete verification.
3. If fault repeats, replace module.

3

Internal fault:
Hardware fault

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

4

Internal fault:
Safety relay key feedback error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

5

Internal fault:
Unstable power (DC) output

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

6

Internal fault:
Invalid processor clock

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

7

Internal fault:
Safety relay drive error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

8

Internal fault:
Zero crossing not detected

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

9

Internal fault:
Flame bias out of range

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

10

Internal fault:
Invalid burner control state

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

This manual is related to the following products: