App1, Appendix 1 - error codes (continued), Cont – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual
Page 95
85
Service Manual NeoTherm 80 - NeoTherm 285
Appendix 1 - Error Codes (continued)
Code Description
L or H Procedure
79
Outlet high limit
H or L 1. Check wiring and correct any possible errors. See
Section B7.
2. Replace the outlet high limit.
3. If previous steps are correct and fault persists, re-
place the module.
80
DHW (Domestic Hot Water) high limit
H or L 1. Check wiring and correct any possible errors.
2. Replace the DHW high limit.
3. If previous steps are correct and fault persists, re-
place the module.
81
Delta T limit
H or L 1. Check inlet and outlet sensors and pump circuits for
proper operation.
2. Recheck the Delta T Limit to confirm proper setting.
3. If previous steps are correct and fault persists, re-
place the module.
82
Stack limit
H or L 1. See Section B20.
2. Check wiring and correct any possible errors.
3. Replace the stack high limit switch.
4. If previous steps are correct and fault persists, re-
place the module.
91
Inlet sensor fault
H
1. Check wiring and correct any possible errors. See
Section B24.
2. Replace the Inlet sensor.
3. If previous steps are correct and fault persists, re-
place the module.
92
Outlet sensor fault
H
1. Check wiring and correct any possible errors. See
Section B26.
2. Replace the outlet sensor.
3. If previous steps are correct and fault persists, re-
place the module.
93
DHW (Domestic Hot Water) sensor fault
H
1. Check wiring and correct any possible errors. See
Section B23.
2. Replace the DHW sensor.
3. If previous steps are correct and fault persists, re-
place the module.
94
Header sensor fault
H
1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, re-
place the module.
95
Stack sensor fault
H
1. Check wiring and correct any possible errors. See
Section B20.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, re-
place the module.
96
Outdoor sensor fault
H
1. Check wiring and correct any possible errors. See
Section B29.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, re-
place the module.
App1
cont.