beautypg.com

App1, Appendix 1 - error codes (continued), Cont – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 101

background image

91

Service Manual NeoTherm 80 - NeoTherm 285

Code Description

L or H Procedure

178

Safety relay on at safe start check

L

Internal fault.
1. Reset module.
2. If fault repeats, replace module.

184

Invalid blower/ HSI output setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

185

Invalid Delta T limit enable setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

186

Invalid Delta T limit response setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

187

Invalid DHW (Domestic Hot Water) high limit

enable setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

188

Invalid DHW (Domestic Hot Water) high limit

response setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

189

Invalid flame sensor type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

192

Invalid igniter on during setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

193

Invalid ignite failure delay setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

194

Invalid ignite failure response setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.\

195

Invalid ignite failure retries setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

Appendix 1 - Error Codes (continued)

App1

cont.

This manual is related to the following products: