B2 - troubleshooting the 24v ac power supply, Troubleshooting the 24v ac power supply, See section b2 – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual
Page 25: Troubleshooting the 24v ac, Power supply, If breaker trips again, Check the 24v power supply, Shooting the 24v ac power supply
15
Service Manual NeoTherm 80 - NeoTherm 285
Troubleshooting the 24V AC Power Supply
24V AC
between TB3
and TB4?
Yes
No
24V AC supply is OK
120V AC
to NT unit?
No
Yes
Troubleshoot the 120V AC
incoming voltage.
120V AC at
main power switch
(3-7 on SW1)?
No
Disconnect power.
Check for continuity through power switch SW1.
Replace if necessary.
Disconnect power.
Check for continuity through primary and secondary
windings of transformer.
Check for short to frame from primary and secondary
windings of transformer.
Replace if necessary.
Reset
circuit bkr. on
transformer
24V OK now?
Yes
24V AC supply is OK
Why did breaker trip?
Loose or damaged wire?
No
Check
for bad
transformer -
Trans. OK?
Yes
B2
This manual is related to the following products: