beautypg.com

B26 - outlet water temperature sensor, Outlet water temperature sensor, Removing and replacing the – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 54: B26 b27

background image

44

Service Manual NeoTherm 80 - NeoTherm 285

Fig. B26-1 - Outlet water temperature sensor (typical)

The outlet water temperature switch allows the control

system to monitor the temperature of the water as it

leaves the NT unit. A typical installation for the outlet

water temperature sensor is shown in Fig. B26-1. The

sensor is connected to J8 8-9-10 on the control module.
This sensor assembly includes two electronic devices

called “thermistors.” As long as the resistance readings

from both sensors agree, the NeoTherm will continue to

operate. If there is a large difference between the read-

ings, or if one of the thermistors is “open” or “shorted,”

the control system will shut down the NT unit and display

a “Hold 92” error message.
For instructions on testing the assembly, see Section

B28.
To reset the control system after the outlet sensor trips:
• On a unit with the original (white) user interface -

Press the Reset button near the lower left-hand

corner of the display. This will reset the lockout, and

the lockout code will disappear.

• On a unit with current user interface -

Reset by pressing the OK button.

Removing and Replacing the Outlet Water Temperature Sensor

See Fig. B26-1 for a typical installation.

Tools and equipment required:
• Crescent wrench or 14 mm socket
• Pipe dope or Teflon® tape

Procedure:
1. Turn off power to the system. Use the main disconnect switch mounted above

the front panel.

2. Isolate the boiler. Turn off the water shutoff valves located upstream and down-

stream of the unit.

3. Drain the boiler. The drain valve is located near the lower end of the heat ex-

changer.

Sensor

Water outlet

pipe

Outlet Water Temperature Sensor

B26

B27

This manual is related to the following products: