beautypg.com

B20 - high stack temperature fault, High stack temperature fault – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 50

background image

40

Service Manual NeoTherm 80 - NeoTherm 285

High Stack Temperature Fault

B20

Yes

No

Correct this immediately.

Blocked exhaust outlet?

Dirty heat exchanger?

If you have the current user interface,

set the stack temperature limit to 190°F.

Actual stack

temperature

problem?

Check the continuity on the wires from

the sensor to J9-4, J9-5, and J9-6 on the

control module.

Wiring to

sensor is correct? Good

connections?

No

Yes

Fault disappears?

No

Replace the control module.

Replace the sensor.

See Section B34

Problem

with circulator

pump?

Yes

No

This manual is related to the following products: