App1, Appendix 1 - error codes (continued) – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 105

background image

95

Service Manual NeoTherm 80 - NeoTherm 285

Appendix 1 - Error Codes (continued)

Code Description

L or H Procedure

232

Invalid pressure sensor type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

234

Invalid outlet high limit enable setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

235

Invalid outlet connector type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

236

Invalid inlet connector type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

237

Invalid DHW (Domestic Hot Water) connec-

tor type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

238

Invalid stack connector type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

239

Invalid header connector type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

240

Invalid outdoor connector type setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.