Unit will not fire - blower is not running – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 13

background image

3

Service Manual NeoTherm 80 - NeoTherm 285

Unit Will Not Fire - Blower is Not Running

A2

cont.

Check programming in controller -

temperature settings, outdoor reset, etc.

See table of code numbers

in Appendix.

Problem indication

from controller?

Yes - Code number

supplied

No

See Section A4

“Control Unit is in Standby Mode”

Controller stuck in

Standby mode?

No

Replace the SOLA controller.

See Section D8, D9

Settings OK?

Yes

Yes

Adjust regulator.

Check with

gas company.

Incoming gas

pressure is

OK?

No

Yes

Correct the settings.

No