beautypg.com

A2 - unit will not fire - blower is not running, Unit will not fire - blower is not running, Unit will not fire, blower is not running – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 12

background image

2

Service Manual NeoTherm 80 - NeoTherm 285

Unit Will Not Fire - Blower is Not Running

A2

No

Yes

Check 120V AC electrical power.

Display is lit?

See Section B2 -

“Troubleshooting the 24V AC

Power Supply”

No

Check for correct “call for heat” signal.

(5-6 on TB7)

See Section B18

“Checking the Blower”

See Section B15

“Checking the Air

Pressure Switch”

Blower-related

problem?

Disconnect sensor for Outdoor Reset

(if used)

No

System operates

normally?

Yes

See Section B29

“Troubleshooting the Outdoor

Reset System”

(continued)

Yes

Yes

Short contacts:

Central Heat: 5-7 on TB7

DHW: 5-6 on TB6

Original user interface shows:

Check, Pre-Purge, Run = Normal operation

Current user interface shows:

Heat demand or DHW = Normal operation

Has call for heat?

No

This manual is related to the following products: