beautypg.com

B29 - troubleshooting the outdoor reset system, B30 - servicing the transformer, Troubleshooting the outdoor reset system – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 56: Servicing the transformer, See section b29, Troubleshooting the outdoor, Reset system, B29 b30

background image

46

Service Manual NeoTherm 80 - NeoTherm 285

Troubleshooting the Outdoor Reset System

Servicing the Transformer

Fig. B30-1 - Transformer installation (typical)

The transformer changes the 120V AC input power

into 24V AC for use by the controls in the NT unit.

The transformer includes an integral 4 Amp circuit

breaker, and is mounted on the machine frame, near

the top of the unit. A reset switch on the bottom of

the unit can be used to reset the circuit breaker.
The transformer is sized for the appliance load only,

and should not be used to supply power to additional

field devices. Additional loads may cause the circuit

breaker to trip.

Yes

Unit starts

running?

Reconnect the sensor lead

Is Outdoor Reset enabled on the controller?

Check programming -

Example - Low boiler temp. set to 130°, heat setpoint set to 120°, so unit never fires.

Example - High and low boiler temps. set the same, so unit never fires.

The high temp. setting must always be higher than the low temp. setting.

Disconnect 1 lead from

outdoor temperature sensor

Note -

On units with the current interface produced before October 2012 -

If the sensor for outdoor reset is disconnected, the unit will operate at the highest setpoint,

as if the outdoor reset function was inoperative.

On units with the current interface produced after October 2012 -

The unit will operate at 140°F.

B29

B30

This manual is related to the following products: