Service Manual NeoTherm 80 - NeoTherm 285

Appendix 1 - Error Codes (continued)

Code Description

L or H Procedure

210

Invalid postpurge time setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

211

Invalid power up with lockout setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

212

Invalid preignition time setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

213

Invalid prepurge rate setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

214

Invalid prepurge time setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

215

Invalid purge rate proving setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

216

Invalid run flame failure response setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

217

Invalid run stabilization time setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

218

Invalid stack limit enable setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

219

Invalid stack limit response setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

220

Unconfigured Delta T limit setpoint setting

L

1. Return to configuration mode and recheck selected

parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

App1

cont.