Chapt.2 Specifications
R0663
R0663
O—
®—
©—
Item
R0663
No. of output point
16 points
Load Voltage
24Vdc, +20%(Max.) /240Vac, +10%(Max.)
Maximum Load
2A/point (resistive load), 1A/point (inductive load),
8A/8 points common
Minimum Load
50mW (5Vdc or more)
Delay
ON Delay
10ms or less
time
OFF Delay
1 Sms or less
Leakage current when OFF
0mA or less
External connections
20-point terminal block
No. of commons
2
Common
configuration
No. of output points
per common
8 point
Common polarity
No polarity
Current consumption
80mA (SVdc) or less
Withstand voltage
1 SOOVac /1 minute
External Relay Coil Power
Required
24Vdc+10%-90mA/all points ON (5mA/ point)
ON/OFF life of relays
Electrical: See the figures of life curves of the output
relay. Mechanical: 20milion times
Weight
Approx. 250g
Circuit Configuration
Terminal Connections
No over load protection fuses
are built into this module.
Therefore connect fuses
externally suitable to the
current capacity.
24Vdc
78
Sequence Controller S2T