Transfer parameter table
Chapt.1 System Configuration
Transfer object
Bank/CH
TYPE
Leading address
Transfer size
Status
flag
u.
0)
w
'u)
0)
u.
3
CL
O
XWATA/ register
0
HOO
0 to 511 (T3H/S2T)
0 to 255 (T3)
0 to 63 (T2/T2E)
1 to 256
(T3H/T3/S2T)
1 to 64
(T2/T2E/T2N)
None
W register
0
H01
0 to 2047 (T3H/T2N/S2T)
0 to 1023(T3/T2/T2E)
1 to 256
None
LW register
0
H02
0 to 255
(T3H/T3/T2/T2E/T2N/S2T)
1 to 256
None
RW register
0
H03
0 to 999 (T3H/S2T)
0 to 511 (T3)
0 to 255 (T2N)
0 to 127 (T2/T2E)
0to63(T1)
1 to 256
(T3H/T3/S2T)
1 to 128
(T2/T2E/T2N)
1 to64(T1)
None
D register
0
H04
0 to 8191
(T3H/T3/T2N/S2T)
0 to 4095 (T2/T2E)
oto 1023(T1)
1 to 256
None
F register
0
H05
0 to 32767 (T3H/S2T)
0 to 8191 (T3)
0 to 1023 (T2/T2E/T2N)
1 to 256
None
Expanded F register
(1C memory card)
1 to 15
(T3H/T3/T2)
H05
0 to 8191
1 to 256
None
1 or 2 (T3H)
H06
0 to 65535 (Bank 1)
0 to 57343 (Bank 2)
1 to 256
None
Expanded F register
(T2E/S2T
internal memory)
1 to 3 (T2E)
1 to 15(S2T)
H05
0 to 8191
1 to 256
None
1 to 8 (S2T)
H06
0 to 65535 (Bank 1 to 7)
0 to 57343 (Bank 8)
1 to 256
None
TOSLINE-S20
scan memory
1 or 2
(T3H/T3/S2T)
1 (T2/T2E)
H10
0 to 1023 (S20)
1 to 256
Yes
TOSLINE-S20LP
scan memory
1 or 2 (T3H/S2T)
1 (T2N)
H10
0 to 4095 (S20LP)
1 to 256
Yes
EEPROM (D register)
0
H20
0 to 8191 (T3H/T3/S2T)
0 to 4095 (T2/T2E/T2N)
0 to 511 (T1)
Source (read):
1 to 256
None
Destination (write):
1 to 128 (T3H/S2T)
1 to 64 (T3)
1 to 32
(T2/T2E/T2N)
1 to 16 (T1)
T2E communication
card / T2N / S2T link port
0
H30
0
1 to 256 *2
Yes
Global variable
0 to 7 (S2T)
H51
0 to 16383 (TC-net)
0 to 32767 (C2)
1 to 256
None
*1) When S20 is transfer source, the scan healthy map is created, (max. 16 words)
In case of S20LP, no status flag is added.
*2) When the link port is transfer source (receiving), the transfer size must be 256 (fixed).
*3) When the link port is transfer source (receiving), 2 words of status flag is added.
When it is destination (transmitting), 1 word of status flag is added.
*4) PU672T has the expansion memory, and use 512k words expanded file resister.
PU662T don’t have the expansion memory, so this function can’t be used.
42
Sequence Controller S2T