Da622&da672 – Toshiba SX 2000 User Manual
Page 120
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
2.3 I/O Module Specification
DA622&DA672
Item
DA622
DA672
No. of output channel
2 channels (N side common)
2 channels (N side common)
Output Range
1-5V, 4-20mA (paired output)
-10-+10V
Load Impedance
1-5V:5KQ or more
4-20mA:600Q or more
5KQ or more
Resolution
1-5V, 4-20mA: 0-4000
-10V-+10V:-2000-+2000
Overall Accuracy
±0.5%FS/25“C
±1%FS/0~55“C
±0.5%FS/25°C
±1%FS/0~55°C
Conversion Cycle
Approx. 1ms/channel
Approx. Ims/channel
External Power Supply
failure detection
None
None
Current consumption
170mA (5Vdc) or less
170mA (5Vdc) or less
Withstand voltage
1500Vac/1 minute
1 SOOVac /1 minute
External Power required
24Vdc±10%-90mA
24Vdc±10%-90mA
Weight
Approx. 250g
Approx. 250g
Circuit Configuration
Terminal Connections
*DA622 only
CH1
CH2
Isolate external power
supply
line
(24Vdc)
from other signal lines.
Use shielded twisted
pair cables for analog
signals.
6F8C0926
1 0 3