Chapt.2 Specifications
R0S62S
R0662S
Item
No. of output point
Load Voltage
Maximum Load
Minimum Load
Delay
time
ON Delay
OFF Delay
Leakage current when OFF
External connections
Common
configuration
No. of commons
No. of output points
per common
Common polarity
Current consumption
Withstand voltage
External Relay Coil Power
Required
ON/OFF life of relays
Weight
R0662S
8 points (each point isolated)
110Vdc, +10%(Max.) /240Vac, +10%(Max.)
2A/point (resistive load) and 1A/point (inductive load) at
240Vac/24Vdc
0.5A/point (resistive load) and 0.1A/point (inductive load) at
110Vdc
50mW (5Vdc or more)
10ms or less
15ms or less
0mA or less
18-point terminal block
1
1 point
No polarity
40mA (5Vdc) or less
1500Vac /1 minute
24Vdc+10%-100mA/all points ON (10mA/ point)
Electrical: See the figures of life curves of the output relay,
Mechanical: 20milion times
Approx. 250g
Circuit Configuration
Terminal Connections
No over load protection fuses
are built into this module.
Therefore connect fuses
externally suitable to the
current capacity.
76
Sequence Controller S2T