8 wiring of the computer link, One to one configuration – Toshiba SX 2000 User Manual
Page 158
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

4.8 Wiring of the computer link
4.8 Wiring of the computer link
Cable connection examples show as below.
• Below figure shows an example of cable connection using the RS-232C/RS-485
converter (ADP-6237B).
• Use shielded twisted-pair cable for data communication suited to RS-485
standard. The cable shield should be connected to single -point ground.
One to one configuration
Master
computer
TXD
RXD
RTS
CTS
SG
DTR
DSR
CD
RS-232C
(max. 15m)
RS-232C/RS-485 converter
(ADP-6237B)
3
RXD
TXA
2
TXD
TXB
5
CTS
RXA
4
RTS
RXB
7
SG
SG
6
DSR
TERM
20
DTR
FG
8
CD
1
FG
25-pin
connector
Terminal
block
---
S2T
30C
RXA
RXB
TXA
TXB
SG
TERM
RS-485
(max. 1km)
Terminal
block
On the S2T, removable terminal block is provided for cable connection.
Short between RXA and TERM for termination at both the S2T and the
ADP-6237B.
If the master has RS-485 (or RS-422) interface and the S2T is connected to the
master directly, connect termination resistor 1/2 W - 1 2 0 Q between RXA and RXB
at the master end.
B
6F8C0926
141