Cpu register o s2t link port – Toshiba SX 2000 User Manual
Page 60
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

1.4 Free ASCII mode
CPU register o S2T link port
Operation:
When the instruction input is ON, one set of message (from start character to
the trailing code) which is received by the link port is read from the receive
buffer, and stored in the CPU registers. The transfer size is fixed to 256
words. The execution status and the message length (in bytes) are stored in
the status flag.
The instruction input must be kept ON until the receiving operation is
complete.
Example:
Source designation
Transfer size
Destination designation
DOOOO
D0001
HOO
H30
D0002
00256 (fixed)
D0005
HOO
H04 1
00000
D0003
Execution status
D0006
00100 1
D0004
Message length
Link port
D0100 (CPU register)
When ROOOO is ON, one set of received message is read and stored in
D0100 and after.
Execution status:
HOOOO .
H0001 .
H0002 .
H0003 .
H0004 .
.. Normal complete
.. Communication error (parity error, framing error)
.. Message length over (more than 512 bytes)
.. Receive buffer over flow
.. Receive timeout (from start character to the trailing code)
Baudrate
Time-out setting
300, 600, 1200 bps
30 seconds
2400 bps
15 seconds
4800 bps
7 seconds
9600 bps
3 seconds
19200 bps
1.5 seconds
Message length:
0......................... No receive message
1 to 512 ... Message length in bytes
Remarks:
The instruction error flag (S0051) comes ON in the following cases, (no
operation)
• The leading address for the link port designation is other than 0.
• Transfer size is other than 256.
• Mode setting of the link port is not the free ASCII mode.
• This instruction is programmed in the sub-program #1.
6F8C0926